← Back to catalog
XHRL12620WFR
CSB

XHRL12620WFR

UPS
AGM/VRLA

12V Top Terminal VRLA-AGM battery. Valve Regulated Lead Acid (VRLA) Battery. Maintenance-Free, Absorbent Glass Mat (AGM) Technology for Efficient Gas Recombination of up to 99%. Pure Lead Construction and Proprietary Elements. Designed for High-Rate UPS, Float Service Standby Power Applications.

Brand
CSB
Application
UPS
Chemistry
AGM/VRLA
Voltage
12
V
Cells
6
Marketed capacity
620
W/cell
15 min to 1.67 VPC @ 25°C (77°F)
W/cell @ 15 min, 1.67 VPC
620
W/cell
Ah @ 8 hr, 1.75 VPC
Ah
Specific gravity
Terminal
I2 thread lead alloy terminal to accept M6 bolt
Dimensions (L × W × H)
13.5
×
6.69
×
10.85
in
Weight
104.03
lb
Notes

Watts per cell to 1.67 VPC @ 25°C: 923.67 (5 min) · 620 (15 min). Max charge current 62.00A; max discharge current 800A (5 sec); short circuit current 3722A; internal resistance approx. 2.40 mΩ. Container: PP (UL 94-HB) & Flame Retardant (94-V0) available upon request. Design life: Up to 10 Years in Standby Service at 25°C. Eurobat (20°C): >12 Years. Built in Accordance with IEC 60896-21/22:2004; UL1973 Listed (MH66728) and UL1989 Recognized (MH14533); Certified by TUV NORD according to ISO 9001:2015.

Similar batteries

Equivalent models from other manufacturers with matching specs.

Request a quote

Tell us how many you need and we'll follow up within one business day. For urgent requests, call 740-549-1540.

Mako Power Inc.

105 Innovation Court, Suite E, Delaware, Ohio 43015

P 740-549-1540 · F (800) 364-6038

Thank you! Your submission has been received!