12V Front Terminal VRLA-AGM battery. Valve Regulated Lead Acid (VRLA) Battery. Maintenance-Free, Absorbent Glass Mat (AGM) Technology for Efficient Gas Recombination of up to 99%. Pure Lead Construction and Proprietary Elements. Designed for High-Rate UPS, Float Service Standby Power Applications.
Watts per cell to 1.67 VPC @ 25°C: 2069.83 (30 sec) · 1403.33 (5 min) · 907.67 (15 min). Max charge current 90.00A; max discharge current 1900A (5 sec); short circuit current 5102A; internal resistance approx. 1.86 mΩ. Container: PP (UL 94-HB) & Flame Retardant (94-V0) available upon request. Design life: Up to 10 Years in Standby Service at 25°C. Eurobat (20°C): >12 Years. Built in Accordance with IEC 60896-21/22:2004, UL1973 Listed (MH66728) and UL1989 Recognized (MH14533); Certified by TUV NORD according to ISO 9001:2015.
Equivalent models from other manufacturers with matching specs.
Tell us how many you need and we'll follow up within one business day. For urgent requests, call 740-549-1540.
Mako Power Inc.
105 Innovation Court, Suite E, Delaware, Ohio 43015
P 740-549-1540 · F (800) 364-6038