12V VRLA-AGM battery. Valve Regulated Lead Acid (VRLA), maintenance-free. Absorbent Glass Mat (AGM) technology, gas recombination up to 99%. Pure lead construction and proprietary elements. Designed for High-Rate UPS, Float Service Standby Power Applications.
Watts per cell to 1.67 VPC @ 25°C: 979.83 (30 sec) · 660.5 (5 min) · 370.17 (15 min). Max charge current 35.00A; max discharge current 900A (5 sec); short circuit current 2616A; internal resistance approx. 3.22 mΩ. Container: PP (UL 94-HB); flame retardant (UL 94-V0) available on request. Design life: Up to 10 years standby at 25°C; Eurobat (20°C): >12 years. Built to IEC 60896-21/22:2004; UL1973 Listed (MH66728); UL1989 Recognized (MH14533); TÜV NORD ISO 9001:2015.
Equivalent models from other manufacturers with matching specs.
Tell us how many you need and we'll follow up within one business day. For urgent requests, call 740-549-1540.
Mako Power Inc.
105 Innovation Court, Suite E, Delaware, Ohio 43015
P 740-549-1540 · F (800) 364-6038