12V Front Terminal VRLA-AGM battery from CSB's XPL-FT (Xtreme Power Long Life) series, purpose-built for high-density data center and mission-critical UPS applications. Maintenance-free AGM with up to 99% gas recombination, pure lead construction and proprietary elements, 30+ second high-rate discharge capability, and an industry-standard 23" front terminal footprint.
Watts per cell to 1.67 VPC @ 25°C: 1766.00 (30 sec) · 1144.17 (5 min) · 642.50 (15 min). Max charge current 58.3A; max discharge current 1550A (5 sec); short circuit current 4132A; internal resistance approx. 2.01 mΩ. Container: PP (UL 94-HB), flame retardant (94-V0) available upon request. Design life up to 10 years in standby service at 25°C (Eurobat at 20°C: >12 years, Very Long Life). Built in accordance with IEC 60896-21/22:2004, UL1973 Listed (MH66728) and UL1989 Recognized (MH14533). Certified by TUV NORD to ISO 9001:2015.
Equivalent models from other manufacturers with matching specs.
Tell us how many you need and we'll follow up within one business day. For urgent requests, call 740-549-1540.
Mako Power Inc.
105 Innovation Court, Suite E, Delaware, Ohio 43015
P 740-549-1540 · F (800) 364-6038